Solid state electronic flame detectors for use with Honeywell Flame Safeguard controls and amplifiers. Sense ultraviolet radiation produced by combustion of gas, oil, coal or other fuels.
- Replace C7012 vacuum tube models
- Mount horizontally, vertically or at any angle in between
- Provide quick electrical hookup with threaded conduit fitting and color-coded leadwires
- Reduced nuisance shutdowns by wiring two in parallel
- C7012E1278 5 pin Brad Harrison type (formally 41307N)mating connector not supplied nor available through Honeywell
Specifications
| Description |
Ultraviolet Flame Detector (Purple Peeper) |
| Type |
Ultraviolet, Purple Peeper, Self-Checking |
| Application |
Coal fired burners |
| Application |
Gas fired burners |
| Application |
Oil fired burners |
| NEMA Rating |
Explosion Proof |
| Lead Length (Inches) |
96 in |
| Lead Length (mm) |
2438 mm |
| Electrical Connections |
6 NEC Class 1 Color-coded leadwires. |
| Ambient Temperature Range (F) |
-20 F to +175 F |
| Ambient Temperature Range (C) |
-20 C to +79 C |
| Mounting |
1 in. NPT |
| Electrical Ratings |
120 Vac |
| Frequency |
60 Hz |
| Frequency |
50 Hz |
| Power Consumption |
7.0 W |
| Dimensions (Inches) |
8 in. diameter x 12 in. long |
| Dimensions (mm) |
203 mm diameter x 305 mm long |
| Weight (LBS) |
14.5 lb |
| Weight (KG) |
6.6 kg |
| Approvals, Underwriters Laboratories Inc |
Listed: File No. E34649, Guide No. ZTSZ |
| Approvals, Canadian Standards Association |
Certified: Master Report LR95329-1 |
| Approvals, Industrial Risk Insurers |
Acceptable |
| Approvals, Factory Mutual |
Approved: Report No. 14740.01 |
| Includes |
N/A |
| Comments |
Dynamic self-checking flame detector, explosion-proof, two piece, violet, cast aluminum enclosure |
| Used With |
Flame Amplifiers: R7247C, R7847C, R7747C |